Compatible Outdoor Unit ModelAC018JXADCH/AA (CXH18ADJ)
Compressor TypeInverter Driven, Twin BLDC Rotary
Cooling at 95F: Maximum Capacity (BTUH)21000
Cooling at 95F: Minimum Capacity (BTUH)5000
Cooling at 95F: Rated Capacity (BTUH)18000
Efficiency: COP at 47F3.1
Guaranteed Operating Voltage Range (VAC)176/254 VAC
Heating at 47F: Maximum Capacity (BTUH)25000
Heating at 47F: Minimum Capacity (BTUH)3800
Heating at 47F: Rated Capacity (BTUH)20000
Indoor Unit: Drain Pipe Size Inch (mm)1-1/16 ID for 3/4 PVC
Indoor Unit: Fan Motor FLA1.1
Indoor Unit: Fan Motor Output (W)153
Indoor Unit: Fan TypeBLDC (1) With Sirocco Fan (2)
Indoor Unit: Fuse/Breaker Size (Amp)15
Indoor Unit: Heat Exchanger Tube Dia. Inch (mm)1/4
Indoor Unit: Refrigerant ControlEEV
Indoor Unit: Sound Pressure Level dB (A)26 / 30 / 34
Outdoor Unit: Compressor RLA6.1
Outdoor Unit: Compressor TypeInverter Driven, Twin BLDC, Rotary
Outdoor Unit: Heat Exchanger Tube Dia. Inch (mm)1/2
Outdoor Unit: Sound Pressure Level dB[A]48/48 (Cooling/Heating)
Piping: Max. Piping Height Difference Feet (m)66
Piping: Max. Piping Length Feet (m)98 '
Power Supply208/230 V/1 Phase/60 Hz
Refrigerant Data: TypeR-410A
Temperature Rating61 to 90 deg F Cooling, <=80 deg F Heating