Temperature Rating5 to 118 deg F, -13 to 109 deg F
Tonnage10
Voltage Rating208 - 230
Additional Information
AHRI Certified|cETLus Listed|UL 1995
Features & Benefits
Construction - The unit shall be EGI (electronic galvanized steel) with a baked on powder coated finish. Some brackets shall be GI (hot-dipped galvanized steel)
Air Side Heat Exchanger - The heat exchanger shall be mechanically bonded fin to copper tube
The aluminum fins of the heat exchanger shall have a protective coating
Salt spray test method: ASTM B117-18 - the heat exchanger showed no unusual rust or corrosion development to 2,280 hours
Water Side Heat Exchanger - The heat exchanger shall be brazed plate type
Controls - The unit shall be operated via NASA Protocol with controls provided by Samsung
Can connect up to 16 X AG0**KSVA*H/AA DVM Chillers to a single DVM Chiller module controller (MCM-A00UN) to provide various system operation configuration, setup, monitoring, status, and error notification (MCM-A00UN is required for operation.)
The outdoor unit shall have a removable EEPROM that stores unit serial number, startup information, system settings, system tag/name, and other information
Controls shall integrate with a BMS without additional interface modules
Control wiring shall be 16 AWG X 2 shielded wire (for communicating controls connections)
Refrigerant System - The compressors shall be Samsung hermetically sealed, inverter driven, direct flash injected, DC scroll type with soft-start capability
The refrigerant system capacity shall modulate based on demand
Flash injected compressors provide advanced low ambient heating performance
Refrigerant flow shall be controlled by EEV (electronic expansion valve)
Asymmetrical scroll design with rotating compressor operation/priority
Optional night quiet modes to reduce outdoor unit sound (default mode and levels 1-3) with automatic or manual activation