Honeywell Temperature Control, T675A Model, 120/240/277 VAC, Copper Bulb Sensor, Configuration: (1) SPDT, Relay Output, 20 ft Capillary Length, 50/60 Hz, 8 A Full Load and 48 A Locked Rotor at 120 VAC, 5.1 A Full Load and 30.6 A Locked Rotor at 240 VAC, 4.2 A Full Load and 25.2 A Locked Rotor at 277 VAC Contact, 3 - 10 deg F Differential, Temperature Settings: 0 - 100 deg F, 2 in L, 5-5/8 in H, 2-5/8 in W, 125 deg F Maximum Operating
Why Create an Account?
Ability to track orders
More Options & Savings
Amazing Customer Service
$518.82Â /Â ea
In Stock
Attributes
Additional Information
Features & Benefits
Documents
Attributes
BrandHoneywell
Capillary Length20
Configuration(1) SPDT, Relay Output
Contact Rating8 A Full Load and 48 A Locked Rotor at 120 VAC, 5.1 A Full Load and 30.6 A Locked Rotor at 240 VAC, 4.2 A Full Load and 25.2 A Locked Rotor at 277 VAC
Differential Temperature3 - 10
Frequency Rating50/60
Height5-5/8
IndustryHVAC
Length2
ModelT675A
Sensor TypeCopper Bulb
Temperature Rating125 deg F Maximum Operating
Temperature Settings0 - 100
Voltage Rating120/240/277
Width2-5/8
Additional Information
UL E4436 volume 4, section 11, guider XAPX, CSA report -1 Certified, UN 1993
Features & Benefits
Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area
Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems
Fast response models operate approximately 4-times faster than standard models
Controller can be-mounted in any position
Ambient temperature compensation provides good temperature control
Refer to T775 electronic remote temperature controller where more exact control is required and/or remote controller location is preferred
T675A models with fixed differential have an electrical rating of 125 V-A at 120/208/240 and 277 VAC
Flammable liquid, 3, II hazmat information
1-sensor inputs